Арт.: FN310

Многофункциональный модуль полевой беспроводной сети FN510

Многофункциональный модуль полевой беспроводной сети FN510 с «Field Wireless Communication Module FN110» может подключаться к полевой беспроводной сети как полевое беспроводное устройство.

Цена по запросу  — уточняйте актуальную стоимость
Power SupplySpecifications Battery
PerformanceSpecifications Update Period
BatteryCharacteristics [Measurement code: A]Typical battery life when using analog input or digital input is 10 years* 1or 7 years* 2and when using digital output with always on is 3 years* 3or 2 years* 1in the following conditions.* 4- Ambient temperature: 23 ±2°C- Device role: IO mode- LCD display: off*1: Update period: 10 s*2: Update period: 5 s*3: Update period : 30 s*4: Environmental condition such as vibration and the type of connected device may affect the battery life.[Measurement code: C]Typical battery life when using piezoelectric accelerometer is 10 years* 5or 2 years* 6in the following conditions.* 7- Ambient temperature: 23 ±2°C- Device role: IO mode- LCD display: off- Sampling frequency: 20 kHz- Sampling points: 1024 points*5: Update period: 60 s*6: Update period: 10s*7: Environmental condition such as vibration and the type of connected device may affect the battery life.
FunctionalSpecifications Input
Output Communication specifications between this product and FN120 are below.Communication Mode: Half-duplex communication (RS485 compliant)Communication Speed: 9600 bpsConnector: 5-pin round connector dedicatedCable: Max 20 m (dedicated cable)
Power Supply Power supply to the FN120Supply voltage: 3.5 VSupply current: 50 mAPower supply to sensors[Measurement code: A] None[Measurement code: C] See Table 2

Технические характеристики

Power SupplySpecifications Battery
PerformanceSpecifications Update Period
BatteryCharacteristics [Measurement code: A]Typical battery life when using analog input or digital input is 10 years* 1or 7 years* 2and when using digital output with always on is 3 years* 3or 2 years* 1in the following conditions.* 4- Ambient temperature: 23 ±2°C- Device role: IO mode- LCD display: off*1: Update period: 10 s*2: Update period: 5 s*3: Update period : 30 s*4: Environmental condition such as vibration and the type of connected device may affect the battery life.[Measurement code: C]Typical battery life when using piezoelectric accelerometer is 10 years* 5or 2 years* 6in the following conditions.* 7- Ambient temperature: 23 ±2°C- Device role: IO mode- LCD display: off- Sampling frequency: 20 kHz- Sampling points: 1024 points*5: Update period: 60 s*6: Update period: 10s*7: Environmental condition such as vibration and the type of connected device may affect the battery life.
FunctionalSpecifications Input
Output Communication specifications between this product and FN120 are below.Communication Mode: Half-duplex communication (RS485 compliant)Communication Speed: 9600 bpsConnector: 5-pin round connector dedicatedCable: Max 20 m (dedicated cable)
Power Supply Power supply to the FN120Supply voltage: 3.5 VSupply current: 50 mAPower supply to sensors[Measurement code: A] None[Measurement code: C] See Table 2
InstallationEnvironment Ambient Temperature Limits
Ambient Humidity Limits Operating: 0 to 100%RH (non-condensation)Storage: 0 to 100%RH (non-condensation)
Ambient Temperature Gradient Operating: ±10°C/h or lessStorage: ±20°C/h or less
Vibration Resistance 0.21 mm P-P (10 - 60 Hz), 3G (60 - 2 kHz)
Shock Resistance 50 G 11 ms
RegulatoryComplianceStatements CE Conformity
Canadian Safety Standards CAN/CSA-C22.2 No.61010-1CAN/CSA-C22.2 No.94.1, CAN/CSA-C22.2 No.94.2IEC 60529
Degrees of Protection IP66, IP67 and Type 4X apply when the connector is properly tightened.
Explosion ProtectedTypes FM (United States or Canada), ATEX, IECEx Intrinsically safe Approval
Physical Specifications Connections
Housing Material Plastic (Polycarbonate)
Weight 500 g (without mounting bracket, clamp, and battery)
Function Item
4-20 mA Analog Input (AI)* 1 Number of input channels
Input signal 0.1 to 3.2 V
Range 0 to 25 mA
Internal shunt resistor 10 Ω
Accuracy ±16 uA
Temperature coefficient ±3.2 uA/10°C
Digital Input (DI)*1*2 Number of input channels
Maximum on resistance 200 Ω
Minimum off resistance 50 kΩ
Current value when contact is on IN1:0.2 mAIN2:1 mA
Digital Output(DO)*1*3 Number of output channels
Output signal Dry contact output
Maximum load current 125 mA DC
Maximum load voltage 30 V DC
Pulse Input (PULSE)*1*2 Number of input channels
Minimum detection time*4 5 ms
Maximum input frequency 100 Hz
Counter range 0 to 999999
AC Analog Input (AI) Number of input channels
Sensing mode*1 Acceleration, Velocity,Velocity LPF160 Hz (Gain High, Gain Low)
Measurement data Peak, RMS, Peak/RMS
Sampling Frequency 1, 2, 5, 10, 20 kHz
Sampling Points 1024, 2048, 4096 points
Frequency range 10 Hz to 10000 Hz
Range*2*3 Acceleration: 0 to 300 m/s2Velocity:0 to 160 mm/s
Accuracy (100 Hz)*4*5 Acceleration: ±(2% of reading + 2 m/s2)Velocity: ± (10% of reading +1 mm/s)
Sensor power supply voltage 3.4 V typ.
Sensor power supply current 10 mA max.
Conditions Accuracy (100 Hz)
Ambient temperature -40 to 85ºC, the entire measurement range Acceleration: -27 to +17% of reading ± 2 m/s* 2rmsVelocity: -35 to +25% of reading ± 1 mm/s rms
Ambient temperature 25±10ºC, the entire measurement range Acceleration: ± (15% of reading + 0.8 m/s* 2rms)Velocity: ± (23% of reading + 0.2 mm/s rms)
Date Remarks
2024/12 Important Notice for Safe Use of Products

Запросить цену на Многофункциональный модуль полевой беспроводной се

Заполните форму — ответим с актуальной ценой и сроком поставки в течение рабочего дня

Похожие позиции